Philips Centium ICN-2S86 SC Programmed Start Electronic Ballast

(No reviews yet) Write a Review
Was: $64.81
Now: $56.67
SKU:
ICN2S86SC-ADV
Condition:
New
Shipping:
$9.97 (Fixed Shipping Cost)
HS Tariff code:
8504.10.0000

Product Overview

Philips Advance Logo

PHILIPS ADVANCE Centium ICN-2S86-SC | 120-277V | (2) F96T8/HO Ballast

Philips Advance Centium ICN-2S86-SC is a heavy-duty programmed-start electronic ballast designed for Slimline and High Output (HO) T8 fluorescent lamps. Engineered with IntelliVolt technology (120-277V), this ballast provides maximum flexibility for industrial and commercial retrofits. Its programmed-start circuitry is specifically designed to extend lamp life in applications with frequent switching cycles, while the parallel circuit design ensures that if one lamp fails, the other remains illuminated. With a robust "SC" housing and UL Type 1 Outdoor rating, it is the ideal choice for demanding warehouse, cold storage, and outdoor signage applications.

Voltage
120-277V
IntelliVolt
Start Type
Programmed
Soft Start
Lamp Qty
1 or 2
F96T8/HO
THD
<10%
Low Distortion
Design
SC-Can
Standard

Product Overview

The Philips Advance Centium ICN-2S86-SC is engineered for high-wattage T8 systems, offering an energy-efficient alternative to traditional magnetic ballasts. Its "Programmed Start" technology pre-heats the lamp electrodes before applying full voltage, reducing the stress on the filaments and allowing for significantly more start cycles without premature failure. This makes it the preferred ballast for use with occupancy sensors. Additionally, the ballast features a Class A sound rating, ensuring quiet operation in professional environments, and is Outdoor Type 1 rated for versatility in cold or damp locations.

  • IntelliVolt Multiple Voltage: Operates on any voltage from 120V to 277V (50/60Hz), reducing inventory needs for facility managers.
  • Parallel Circuitry: Lamps operate independently; if one lamp fails, the remaining lamp continues to function, ensuring consistent light levels.
  • Programmed Start: Soft-start technology maximizes lamp life, particularly in areas with frequent on/off switching.
  • High Output Efficiency: Optimized for F96T8HO lamps, delivering maximum lumens while maintaining low total harmonic distortion (THD).

Lamp Compatibility

This versatile ballast is rated to operate the following T8 lamp configurations:

  • F96T8 High Output: (1 or 2) F96T8HO (8ft), F96T8-49W, F96T8/WM, or F96T8/WMP
  • Medium T8 High Output: (1 or 2) F72T8HO, F60T8HO, or F48T8HO
  • Standard T8: (1 or 2) F58T8 or F40T8

Technical Specifications

  • Brand: Philips Advance Centium
  • Model: ICN-2S86-SC (ICN2S86SC)
  • Input Voltage: 120-277V AC (50/60Hz)
  • Starting Method: Programmed Start
  • Ballast Factor: High
  • Total Harmonic Distortion (THD): <10%
  • Case Temperature (Max): 70°C (158°F)
  • Sound Rating: Class A (20-24 dB)
  • Compliance: RoHS Compliant, UL Type 1 Outdoor, FCC 47 CFR Part 18 Non-Consumer

Safety & Installation Notes

  • Wiring: Always follow the specific wiring diagram on the ballast label for 1-lamp vs 2-lamp operation.
  • Fixture Rating: Rated for enclosed fixtures; UL Type 1 Outdoor rating makes it suitable for use in signs and damp locations.
  • Grounding: Ensure the ballast case is properly grounded to the fixture housing for safe operation and EMI suppression.
  • Cold Starting: Specifically designed to handle the starting requirements of High Output lamps in cooler environments.