GE 63052 GEMH400MVA-F

(No reviews yet) Write a Review
$147.13
SKU:
GEL63052
UPC:
43168630528
Availability:
3-5 Business Days lead time for delivery
Shipping:
Calculated at Checkout
HS Tariff code:
8504.10.0000

Product Overview

GE Lighting Logo

GE 63052 GEMH400MVA-F

The GE 63052 GEMH400MVA-F is a GE Enclosed and Potted Metal Halide F-Can ballast. It is a Magnetic – F-Can ballast designed to operate 1 – 400W M59 120/277 Enclosed and Potted F-Can lamp configuration, with 120/277 dual-voltage input and HX-HPF circuit type. This model is the current-production replacement for GE ballast 42670 (1110-247SC-TC, 400W M59); per GE's F-Can transition plan, it is a direct functional substitute for that part.

This ballast should be selected by matching the GE order code, ANSI lamp code, wattage, input voltage, wiring diagram, and case dimensions to the existing ballast or fixture label.

Wattage
400W
Metal Halide
Voltage
120/277
Dual Voltage
ANSI Code
M59, H33
Lamp Code
Circuit Type
HX-HPF
HID Ballast
Ballast Type
Magnetic
F-Can

Product Overview

GE Enclosed and Potted Metal Halide F-Cans combine the rugged durability and efficiency of high intensity discharge ballasts with the user-friendly envelope of a standard fluorescent-style ballast case, allowing for easier handling and mounting in exterior applications. GE F-Cans are made from high-grade steel laminations and tightly wound, vacuum-impregnated copper coils for superior heat dissipation and water resistance, encased in potting material for additional heat sinking and weather resistance, and secured in a durable white steel powder-coated box for corrosion protection and long life. This construction gives GE F-Cans cooler operating temperatures and better sound attenuation than standard core-and-coil ballasts, making them well suited to remote-mounted, indoor, and outdoor HID applications.

Technical Specifications

BrandGE Lighting
GE Order Code63052
ModelGEMH400MVA-F
Ballast TypeMagnetic – F-Can
ANSI Lamp Code(s)M59, H33
Circuit TypeHX-HPF
Input Voltage120/277
Line Voltage Regulation±5%
Supply Current Frequency60 Hz
Insulation Class90C
Capacitor Temperature Rating100°C (212°F)
Sound RatingC (31-36 decibels)
Additional InfoThermally Protected
Coil Material (Pri/Sec)CU/CU
Dimensions (L x W x H)21.6 in (549 mm) x 3.2 in (81 mm) x 2.6 in (67 mm)
Mounting Length21.0 in (533 mm)
Mounting Width2.0 in (51 mm)
Mounting Slots0.2 in (6 mm)
Weight23.00 lbs
Exit TypeSide
Lead LengthsBlack and White, Red, Black/Yellow – 12 in (305 mm) each
Wiring Diagram ReferenceHID H34
Case Drawing ReferenceFCAN4
Items per Sales Unit / Standard Package1 / 2

Specifications by Line Voltage – Lamp: M59, H33 – 360W Quartz Metal Halide / 400W Quartz Metal Halide / 400W Mercury

Specification120V277V
System Wattage (W)445446
Nominal Current3.90 A1.70 A
Ballast Factor11
Ballast Efficiency Factor0.880.88
Max Input Current3.90 A1.70 A
Starting Current2.50 A1.00 A
Open Circuit Voltage300V300V
Drop Out Voltage66V222V
Power Factor≥90%≥90%
Min. Starting Temperature-22°F / -30°C-22°F / -30°C
Fuse Rating105
Safety ListingcUL ListedUL Listed

Key Features

  • Dual Voltage 120/277V 60 Hz input.
  • Igniter and capacitor mounted within the ballast case.
  • Ideal for external use – UL & cUL 1029 Listed for Type 1 indoor & outdoor applications.
  • Class A Insulation Material – 105°C/221°F rating, 90°C/194°F max case temperature.
  • Reliable low-temperature starting down to -22°F.
  • Standard F-Can dimensions equivalent to competitive offerings for ease of retrofit.
  • Integral thermal protector provides system protection in the event of overload or failure.
  • 2 year limited warranty.

Compatible Applications

  • Commercial and office lighting
  • Retail lighting
  • Education – schools and auditoriums
  • Museum and landmark lighting
  • Down-lighting
  • Indirect lighting

Before Ordering Verify

  • Exact GE Model: Match GE 63052 / GEMH400MVA-F to the existing ballast label or fixture documentation.
  • ANSI Lamp Code: Confirm the fixture lamp is coded M59, H33.
  • Wattage: Confirm the lamp wattage matches 400W.
  • Input Voltage: Confirm the fixture supply matches 120/277.
  • Wiring Diagram: Follow HID H34 on the ballast label and verify socket/lamp holder type before installation.
  • Case Size: Confirm the ballast channel has room for the 21.6 in (549 mm) x 3.2 in (81 mm) x 2.6 in (67 mm) case (mounting length 21.0 in (533 mm)).
  • Cross-Reference: If replacing GE 42670 (1110-247SC-TC, 400W M59), confirm this current-production model is the correct direct substitute for your fixture.

Safety & Installation Guidelines

  • Qualified Installation: Ballasts should be installed by qualified personnel following applicable electrical codes.
  • Disconnect Power: Turn off and lock out power before removing or installing a ballast.
  • Grounding: Properly ground the ballast and fixture to reduce EMI/RFI and support safe operation.
  • Wiring Diagram: Follow HID H34 exactly; incorrect wiring can prevent starting or damage the ballast and lamp.
  • Remote Mounting: When remote mounting, keep lead length and wire gauge within the manufacturer's listed remote mounting distance and wire gauge for this model.
  • Enclosure Integrity: Confirm the potted enclosure and gasket/case seal are intact before installing in outdoor or wet-location fixtures.

Wholesale & Project Support

ADL Supply supports contractors, facility managers, maintenance departments, and commercial buyers with GE HID ballast replacement identification, project quoting, and volume order support.

For volume pricing, availability, or help confirming the correct GE F-Can replacement ballast, contact ADL Supply at 1-800-235-3489.

Reviews