Product Overview
![]()
GE 63048 GEMH100MVR-F
The GE 63048 GEMH100MVR-F is a GE Enclosed and Potted Metal Halide F-Can ballast. It is a Magnetic – F-Can ballast designed to operate 1 – 100W M90 120/277 Enclosed and Potted F-Can lamp configuration, with 120/277 dual-voltage input and HX-HPF circuit type. This model is the current-production replacement for GE ballast 86574 (11210239CTC0001, 100W M90); per GE's F-Can transition plan, it is a direct functional substitute for that part.
This ballast should be selected by matching the GE order code, ANSI lamp code, wattage, input voltage, wiring diagram, and case dimensions to the existing ballast or fixture label.
Wattage 100W Metal Halide | Voltage 120/277 Dual Voltage | ANSI Code M90 Lamp Code | Circuit Type HX-HPF HID Ballast | Ballast Type Magnetic F-Can |
Product Overview
GE Enclosed and Potted Metal Halide F-Cans combine the rugged durability and efficiency of high intensity discharge ballasts with the user-friendly envelope of a standard fluorescent-style ballast case, allowing for easier handling and mounting in exterior applications. GE F-Cans are made from high-grade steel laminations and tightly wound, vacuum-impregnated copper coils for superior heat dissipation and water resistance, encased in potting material for additional heat sinking and weather resistance, and secured in a durable white steel powder-coated box for corrosion protection and long life. This construction gives GE F-Cans cooler operating temperatures and better sound attenuation than standard core-and-coil ballasts, making them well suited to remote-mounted, indoor, and outdoor HID applications.
Technical Specifications
| Brand | GE Lighting |
| GE Order Code | 63048 |
| Model | GEMH100MVR-F |
| Ballast Type | Magnetic – F-Can |
| ANSI Lamp Code(s) | M90 |
| Circuit Type | HX-HPF |
| Input Voltage | 120/277 |
| Line Voltage Regulation | ±5% |
| Supply Current Frequency | 60 Hz |
| Insulation Class | 90C |
| Capacitor Temperature Rating | 100°C (212°F) |
| Sound Rating | B (25-30 decibels) |
| Additional Info | Thermally Protected |
| Coil Material (Pri/Sec) | CU/CU |
| Dimensions (L x W x H) | 11.75 in (299 mm) x 3.2 in (81 mm) x 2.6 in (67 mm) |
| Mounting Length | 11.1 in (283 mm) |
| Mounting Width | 2.0 in (51 mm) |
| Mounting Slots | 0.2 in (6 mm) |
| Weight | 11.00 lbs |
| Exit Type | Side |
| Remote Mounting Distance to Lamp | 10 ft |
| Remote Mounting Wire Gauge | 18 AWG |
| Lead Lengths | Black and White, Red, Black/Yellow – 12 in (305 mm) each |
| Wiring Diagram Reference | HID H34 |
| Case Drawing Reference | FCAN1 |
| Items per Sales Unit / Standard Package | 1 / 4 |
Specifications by Line Voltage – Lamp: M90 – 100W Ceramic Metal Halide / 100W Quartz Metal Halide
| Specification | 120V | 277V |
| System Wattage (W) | 122 | 125 |
| Nominal Current | 1.07 A | 0.47 A |
| Ballast Factor | 1 | 1 |
| Ballast Efficiency Factor | 0.80 | 0.80 |
| Max Input Current | 1.07 A | 0.47 A |
| Starting Current | 1.10 A | 0.50 A |
| Open Circuit Voltage | 250V | 250V |
| Drop Out Voltage | 96V | 222V |
| Power Factor | ≥90% | ≥90% |
| Min. Starting Temperature | -22°F / -30°C | -22°F / -30°C |
| Fuse Rating | 8 | 4 |
| Safety Listing | cUL Listed | UL Listed |
Key Features
- Dual Voltage 120/277V 60 Hz input.
- Igniter and capacitor mounted within the ballast case.
- Ideal for external use – UL & cUL 1029 Listed for Type 1 indoor & outdoor applications.
- Class A Insulation Material – 105°C/221°F rating, 90°C/194°F max case temperature.
- Reliable low-temperature starting down to -22°F.
- Standard F-Can dimensions equivalent to competitive offerings for ease of retrofit.
- Integral thermal protector provides system protection in the event of overload or failure.
- 2 year limited warranty.
Compatible Applications
- Commercial and office lighting
- Retail lighting
- Education – schools and auditoriums
- Museum and landmark lighting
- Down-lighting
- Indirect lighting
Before Ordering Verify
- Exact GE Model: Match GE 63048 / GEMH100MVR-F to the existing ballast label or fixture documentation.
- ANSI Lamp Code: Confirm the fixture lamp is coded M90.
- Wattage: Confirm the lamp wattage matches 100W.
- Input Voltage: Confirm the fixture supply matches 120/277.
- Wiring Diagram: Follow HID H34 on the ballast label and verify socket/lamp holder type before installation.
- Case Size: Confirm the ballast channel has room for the 11.75 in (299 mm) x 3.2 in (81 mm) x 2.6 in (67 mm) case (mounting length 11.1 in (283 mm)).
- Cross-Reference: If replacing GE 86574 (11210239CTC0001, 100W M90), confirm this current-production model is the correct direct substitute for your fixture.
Safety & Installation Guidelines
- Qualified Installation: Ballasts should be installed by qualified personnel following applicable electrical codes.
- Disconnect Power: Turn off and lock out power before removing or installing a ballast.
- Grounding: Properly ground the ballast and fixture to reduce EMI/RFI and support safe operation.
- Wiring Diagram: Follow HID H34 exactly; incorrect wiring can prevent starting or damage the ballast and lamp.
- Remote Mounting: When remote mounting, keep lead length and wire gauge within the manufacturer's listed remote mounting distance and wire gauge for this model.
- Enclosure Integrity: Confirm the potted enclosure and gasket/case seal are intact before installing in outdoor or wet-location fixtures.
Wholesale & Project Support
ADL Supply supports contractors, facility managers, maintenance departments, and commercial buyers with GE HID ballast replacement identification, project quoting, and volume order support.
For volume pricing, availability, or help confirming the correct GE F-Can replacement ballast, contact ADL Supply at 1-800-235-3489.